Every check below is read straight out of the rule engine when this page is built. Nothing here is written by hand, so nothing here can outlive the check it describes. Each one lists the code section it cites and, beside it, the edge it does not reach.

37code checks
20buildability advisories
83metros with their own data
50state baselines

Advisories are counted separately on purpose. They are notes about cost and crew time, and folding them into the code total would inflate how much code checking actually happens.

Structure

14 checks
Design load (snow)Code check

Whether ground snow, from the design or the place, is more than the live load — and so governs every span, ledger and footing check — and whether it is past the 70 psf the prescriptive provisions stop at.

Does not cover: Sizes for snow by scaling the 40 psf tables (spans by the square root of the load ratio, ledger spacing by the ratio). It does not read the snow columns of any adopted table, model drifting or sliding snow, or reduce ground snow to a roof-style deck load.

CitesIRC 2021 R301.2.3
BasisCalculated from the design
Needs from youground snow load · live load · dead load
Joist spanCode check

Whether the joists can span from the house to the beam at the size, spacing and species chosen.

Does not cover: Tabulated at 40 psf live + 10 psf dead, No. 2 grade. It does not size joists for snow, a hot tub, a roof, or any other concentrated load — those escalate the project out of prescriptive scope instead.

CitesIRC 2021 R507.6 / AWC DCA6 Table 1
BasisPublished span/size table
Needs from youdeck depth · joist size · joist spacing · species
Joist cantileverCode check

Whether the joist overhang past the beam is within the fraction of back-span the tables allow.

Does not cover: Checks the overhang length only. It does not check uplift at the inboard end, or a cantilever carrying a guard post, a stair, or a concentrated load.

CitesIRC 2021 R507.6 / AWC DCA6
BasisPublished span/size table
Needs from youdeck depth · beam setback · joist size
Beam spanCode check

Whether each beam line — the outer beam, a house-side beam, and an intermediate beam when there is one — can carry its tributary load between posts at the size and ply count chosen.

Does not cover: Prescriptive tables only. Beams outside the tabulated sizes or species get no verdict, and no engineered beam (LVL, steel, flitch) is modelled. A beam carrying more than 18' of joist span is past the table and fails rather than being read at the 18' column. An intermediate beam is read at the two bays either side added together, a conservative reading of a table written for a beam at the end of a joist span, with each bay taken as a simple span.

CitesIRC 2021 R507.5 / AWC DCA6 Table 2
BasisPublished span/size table
Needs from youdeck width · post count · beam size · beam plies · species · intermediate beam line
Post heightCode check

Whether the posts are within the maximum unbraced height for their size.

Does not cover: Height against a table, nothing more. It does not design bracing, check the post-to-beam connection capacity, or account for wind or seismic load on tall posts.

CitesIRC 2021 Table R507.4
BasisPublished span/size table
Needs from youheight above grade · post size · footing depth
Footing sizeCode check

Whether the footing's bearing area is enough for the load it carries on the local presumptive soil.

Does not cover: Uses one presumptive soil bearing value for the jurisdiction. It is not a soils investigation: expansive soil, fill, a slope, or a high water table can all make a compliant footing wrong.

CitesIRC 2021 R507.3.1
BasisCalculated from the design
Needs from youdeck size · post count · footing size · location
Footing thicknessCode check

Whether the concrete footing is at least the 6-inch minimum thickness.

Does not cover: Thickness against the code minimum only. A footing carrying a heavy load on a large pad may need to be thicker than 6 inches to spread that load without cracking; that is a design check, not a minimum, and is not made here.

CitesIRC 2021 R403.1.1
BasisCalculated from the design
Needs from youfooting thickness
Frost depthCode check

Whether the footing bears below the frost line recorded for the jurisdiction.

Does not cover: Compares against the frost depth in our jurisdiction data, which is a state or metro figure. Confirm the required depth with the building department — it is one of the most commonly amended local numbers.

CitesIRC 2021 R403.1.4 / R507.3
BasisLocal jurisdiction data
Needs from youfooting depth · location
Shape within prescriptive scopeCode check

Whether the outline is a shape the prescriptive framing model can actually frame and check.

Does not cover: This is the check that refuses rather than answers. Angled and curved edges are detected and stopped here; no framing is generated for them and no other check should be read as covering them.

CitesIRC 2021 R507.1 (scope) / AWC DCA6 §1
BasisMeasured from the drawing
Needs from youdeck outline
Decking spanCode check

Whether the joists are close enough together for the decking laid across them.

Does not cover: Assumes boards laid perpendicular to the joists; the Surface Designer's pattern check (DK2) covers a diagonal lay. The composite limit is the typical manufacturer figure, not a code table — the product's own install guide governs and must be checked.

CitesIRC 2021 R507.7
BasisPublished span/size table
Needs from youdecking type · joist spacing
Decking pattern spanCode check

Whether the joists are close enough for the way the boards are laid — on the diagonal, or a product with its own spacing limit.

Does not cover: Uses each catalog product's published spacing for perpendicular and 45° lays, or the type's typical figure when no product is chosen. Manufacturer install guides govern and change; a 90° lay (boards along the joists) is checked against the blocking rows the layout adds, not against sleepers.

CitesIRC 2021 R507.7
BasisPublished span/size table
Needs from youdecking pattern · decking type · joist spacing
Board-end bearingCode check

Whether every board joint in the pattern lands on a joist or on blocking the layout adds.

Does not cover: Reads the layout's own joints: boards are split at joists or at blocking it places. It does not check fastener edge distance at the joint or the bearing of a board end on a doubled joist narrower than the two ends need.

CitesIRC 2021 R507.7
BasisMeasured from the drawing
Needs from youdecking pattern · joist spacing
Built-in loadCode check

Whether a hot tub, planter, kitchen, bench or fire table puts more weight on its own footprint than the span tables' uniform live load.

Does not cover: Weights are typical figures for each kind of built-in, stated with the result; the product's own spec sheet governs. It flags the load and estimates the joist spacing it would need — it does not design the framing under it.

CitesIRC 2021 R301.5
BasisCalculated from the design
Needs from youbuilt-ins · built-in sizes · live load
Hot-tub opening framingCode check

Whether a hot tub set into the deck leaves its opening framed with doubled headers and trimmers clear of every beam line.

Does not cover: Doubles the headers and trimmers and counts the tail joists and hangers. It does not size the headers for their load or design the slab the tub sits on.

CitesIRC 2021 R502.10
BasisMeasured from the drawing
Needs from youbuilt-ins · joist layout · beam lines

Ledger & attachment

4 checks
Ledger fastenersCode check

Whether the ledger fastener type and spacing match the schedule for this deck's span.

Does not cover: Assumes a sound 2-inch nominal band joist on a wood-framed wall. It cannot check what the ledger is actually attached to — brick veneer, stucco, a cantilevered floor, or a rim that has rotted are all beyond it, and all require field verification.

CitesIRC 2021 R507.9.1.1IRC 2021 Table R507.9.1.3(1)
BasisPublished span/size table
Needs from youattachment method · fastener type · fastener spacing · deck depth
Ledger flashingCode check

Whether flashing has been recorded at the ledger.

Does not cover: It checks that you recorded flashing, not that it is correct. Lapping with the weather-resistive barrier, end dams and material compatibility are all field items no drawing can settle.

CitesIRC 2021 R507.2.4
BasisOnly what you record
Needs from youattachment method · flashing recorded
Lateral load connectionCode check

Whether a lateral load path has been recorded for a ledger-attached deck.

Does not cover: Presence, not capacity. Whether the hold-downs actually reach sound floor framing inside the house is a field verification, and the alternate bracing methods the code allows are not modelled.

CitesIRC 2021 R507.9.2
BasisOnly what you record
Needs from youattachment method · lateral connection recorded
Level ledger on the houseCode check

Whether a level marked as ledgered actually sits against the house it would bolt to.

Does not cover: Only checks that the level starts on the house line. The ledger itself is then checked by the ledger rules run on that level as its own deck.

CitesIRC 2021 R507.9
BasisMeasured from the drawing
Needs from youlevels · attachment

Guards

5 checks
Guard requiredCode check

Whether each open edge more than 30 inches above grade carries a guard, judged edge by edge from the corner heights.

Does not cover: Each edge is judged by the taller of its two recorded corners. On sloping ground the governing point may be a corner you have not measured, and a low spot between corners is not seen.

CitesIRC 2021 R312.1.1
BasisMeasured from the drawing
Needs from youheight above grade · guard present · guarded edges
Guard heightCode check

Whether the guard reaches the 36-inch minimum where one is required.

Does not cover: Height only. The guard post attachment that resists the load is not checked — that connection is a common failure point and is outside what DeckForge decides.

CitesIRC 2021 R312.1.2
BasisMeasured from the drawing
Needs from youguard height
Guard openingsCode check

Whether the guard infill rejects a 4-inch sphere: baluster spacing under 4 inches, and some infill at all where a guard is required.

Does not cover: Checks even baluster spacing, the absence of infill, and the recorded cable spacing and run, edge by edge where the guard is styled per edge. Cable still gets a warning to verify on site, because deflection under load cannot be measured from a drawing; the triangular opening at a stair and the gap under the bottom rail are not evaluated.

CitesIRC 2021 R312.1.3
BasisMeasured from the drawing
Needs from youguard infill type · baluster gap · cable spacing and run
Glass infill glazingCode check

Whether glass guard infill is recorded as safety glazing (tempered or laminated), which a guard is required to be.

Does not cover: Reads only what was declared. It cannot see the panel, its thickness, its mark or its fixing, and it does not size the glass or its clamps for the guard load.

CitesIRC 2021 R308.4.4
BasisOnly what you record
Needs from youguard infill type · glass glazing declaration
Gate placementAdvisory

Whether each gate sits in an unbroken run of guard on a guarded edge, fits its edge, and closes itself.

Does not cover: Checks where the gate is drawn against the stair openings and the other gates. Hinge hardware, latch strength and swing direction are not evaluated, and no residential code requires a deck gate to self-close — that is good practice, not a verdict.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from yougates · guarded edges · stair position

Stairs

12 checks
Step between levelsCode check

Whether the drop between two levels that share an edge is either flush or a real step, and whether the lower level has room for the treads plus a landing.

Does not cover: Sizes the step at the tallest riser allowed (7¾") with 11" treads running straight into the lower level across the shared edge. Heights are compared as given, so both levels must be measured from the same ground datum.

CitesIRC 2021 R311.7.5.1IRC 2021 R311.7.6
BasisMeasured from the drawing
Needs from youlevels · level heights · shared edges
Riser heightCode check

Whether the rise actually built — the drop divided by the riser count — is within 7¾ inches.

Does not cover: Derived from the deck height, so it is only as good as that measurement. The code's ⅜-inch tolerance between the tallest and shortest riser is a built-work check no drawing can make.

CitesIRC 2021 R311.7.5.1
BasisCalculated from the design
Needs from youheight above grade · riser count
Tread depthCode check

Whether treads are at least 10 inches nosing to nosing.

Does not cover: Rectangular treads on a straight flight. Winders and their varying depth are not modelled.

CitesIRC 2021 R311.7.5.2
BasisMeasured from the drawing
Needs from youtread depth
Stair widthCode check

Whether the stairway is at least 36 inches wide.

Does not cover: Compares the recorded width. It does not subtract the projection of a handrail, which the code allows only up to 4½ inches.

CitesIRC 2021 R311.7.1
BasisMeasured from the drawing
Needs from youstair width
HandrailCode check

Whether a stair of four or more risers has a handrail, at a height between 34 and 38 inches.

Does not cover: Presence and height. Graspability, continuity over the full flight, and the returns at each end are field items.

CitesIRC 2021 R311.7.8
BasisMeasured from the drawing
Needs from youriser count · handrail present · handrail height
Stair guardCode check

Whether a flight rising more than 30 inches has a guard of at least 34 inches on its open sides.

Does not cover: Height only, and only where the total rise is recorded. Guard post attachment is not checked.

CitesIRC 2021 R312.1.2
BasisMeasured from the drawing
Needs from youheight above grade · stair guard present · stair guard height
Stair guard openingsCode check

Whether stair guard infill rejects the 4⅜-inch sphere allowed on stairs.

Does not cover: Raised as a warning, not a failure, because it reads the deck's baluster spacing — the stair guard may be built to a different spacing that nothing here records. The triangular opening formed by tread, riser and bottom rail is not checked.

CitesIRC 2021 R312.1.3
BasisMeasured from the drawing
Needs from youguard infill type · baluster gap
Open risersCode check

Whether the opening under each tread rejects a 4-inch sphere, where risers are open.

Does not cover: Only runs on a stair recorded as having open risers. A stair built with open risers that nobody recorded is not caught — DeckForge cannot infer this from anything else in the design.

CitesIRC 2021 R311.7.5.3
BasisOnly what you record
Needs from youopen risers recorded · riser count
Flight riseCode check

Whether a single flight climbs more than the 151 inches allowed between landings.

Does not cover: It can tell you a flight is too tall. It cannot lay out the intermediate landing that would fix it — that needs a designer.

CitesIRC 2021 R311.7.3
BasisCalculated from the design
Needs from youheight above grade
Landing at the bottomCode check

Whether a landing at least 36 inches deep and as wide as the stair is recorded at the bottom of the flight.

Does not cover: An unrecorded landing is a warning rather than a failure on purpose: an existing patio or pad at the bottom often already qualifies, and DeckForge cannot see the ground there. Only a landing you have recorded as undersized is failed.

CitesIRC 2021 R311.7.6
BasisOnly what you record
Needs from youlanding recorded · landing depth · landing width · stair width
Mid landing sizeCode check

Whether the landing between the two flights of an L-turn or switchback is at least 36 inches deep and as wide as the stair.

Does not cover: Checks the landing's plan size only. Its framing, the posts and footings under it, and the guard on its open sides are counted but not engineered.

CitesIRC 2021 R311.7.6
BasisMeasured from the drawing
Needs from youstair kind · mid landing depth · stair width
Headroom under the deckCode check

Whether a stair flight that runs back under the deck keeps 6 feet 8 inches between each tread and the deck framing above it.

Does not cover: Measures from the deck's joists down to the tread top. A beam, light or anything else hung lower under the deck is not seen.

CitesIRC 2021 R311.7.2
BasisMeasured from the drawing
Needs from youstair kind · deck height · joist size

House & openings

4 checks
Door not blockedCode check

Whether the deck leaves each recorded exterior door usable rather than framing across it.

Does not cover: Only doors you have recorded on the house wall. An opening not entered is an opening not checked, and the threshold-to-deck step down is not evaluated.

CitesIRC 2021 R311.2
BasisMeasured from the drawing
Needs from youhouse wall openings · deck outline
Stair clear of a doorwayCode check

Whether a stair opening lands immediately in front of a door.

Does not cover: Plan geometry only, for recorded openings. Door swing direction is not modelled.

CitesIRC 2021 R311.3
BasisMeasured from the drawing
Needs from youhouse wall openings · stair placement
Bay window over the ledgerCode check

Whether a bay window or other projection interrupts the wall the ledger needs to attach to.

Does not cover: Flags the conflict; it does not design the fix. Framing around a projection, or converting that bay to freestanding support, is a design decision.

CitesIRC 2021 R507.9.1 (ledger attachment)
BasisMeasured from the drawing
Needs from youhouse wall openings · attachment method
Guard across a doorAdvisory

Whether a required guard would run across a recorded doorway.

Does not cover: A buildability warning, not a code verdict — it points at a conflict between two things that are each individually compliant. Resolving it is a layout decision.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youhouse wall openings · guard present

Buildability

15 checks
Grooved edge exposedAdvisory

Whether hidden-fastener (grooved) boards would end up with their groove showing at an exposed deck edge.

Does not cover: Appearance and fastening advice only; it reads the chosen product's edge profile, not what was actually ordered.

CitesNo code section — this is advice, not a verdict
BasisOnly what you record
Needs from youdecking pattern · decking product
Sliver piecesAdvisory

Whether the pattern produces board pieces too short or too narrow to fasten well.

Does not cover: Counts pieces under 12 inches long or 2 inches wide in the generated layout. A crew may lay out differently and avoid or create slivers the layout does not show.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youdecking pattern
Patterned field borderAdvisory

Whether a herringbone, chevron or parquet field is framed by a border rather than ending in cut pieces at the deck edge.

Does not cover: Only checks that a border exists. It does not judge how the cut pieces at the border look, or whether the border boards suit the pattern's colour.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youdecking pattern · border rows
Zone and inlay placementAdvisory

Whether every zone and inlay sits inside the field and clear of the others, so the layout can include it.

Does not cover: Checks the shape's outline against the field and the other shapes only. Furniture, doors, stairs and hatches over an inlay are not considered.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youzones · inlays · border rows
Box step heightAdvisory

Whether box or wraparound steps are being used for a rise where stacked boxes become heavy and hard to keep square.

Does not cover: A rule of thumb at 30 inches of rise. It does not size the boxes' framing, check what the lowest box bears on, or decide the guard on a box stair's open ends.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youstair kind · deck height
Curved edgeAdvisory

Whether a curved edge is gentle enough to build as a laminated rim with bent boards, whether every curve asked for could be drawn, and whether a stair leaves from a curve.

Does not cover: Uses a 4-foot radius as a rule of thumb; the board maker's own minimum bend radius governs. It does not design the rim lamination or check the bent boards' fastening.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youcurved edges · deck outline
Built-in clearancesAdvisory

Whether a fire table sits clear of the house wall and whether a privacy screen is tall enough to need a wind check.

Does not cover: Uses a 36-inch clearance and a 6-foot screen height as rules of thumb. The product's own clearances, overhead clearance and gas-line routing are not checked.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youbuilt-ins · house wall
Built-in placementAdvisory

Whether every built-in sits fully on the deck.

Does not cover: Checks the built-in's rectangle against the deck outline only; doors, stairs and walkways it might block are not considered.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youbuilt-ins
Level placementAdvisory

Whether each extra level meets another one edge to edge, rather than floating apart or sitting over it.

Does not cover: Compares the level rectangles with the main outline and each other in plan only. A level over another one is flagged and escalated; its framing is not designed.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youlevels · deck outline
Beam splices over postsAdvisory

Whether beam splices land over a post rather than in a span.

Does not cover: A warning about layout, not a capacity check. DeckForge does not evaluate the strength of any splice, and a splice landing over a post is not thereby verified.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youdeck width · post count · beam stock length
Sliver deck boardAdvisory

Whether the last deck board would be ripped to an awkwardly narrow strip.

Does not cover: Appearance and fastening practicality only. It has no bearing on compliance.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youdeck depth · board width
Stringer throatAdvisory

Whether enough uncut material remains behind the stair notches.

Does not cover: Cites the DCA6 guidance figure as a rule of thumb and is reported as a warning. It is not a stringer capacity calculation, and DeckForge does not size stringers.

CitesNo code section — this is advice, not a verdict
BasisCalculated from the design
Needs from youriser count · tread depth · stringer stock size
Lumber wasteAdvisory

Whether the cut plan wastes an unusual proportion of the stock purchased.

Does not cover: Cost signal only. It says nothing about whether the deck is compliant or buildable.

CitesNo code section — this is advice, not a verdict
BasisCalculated from the design
Needs from youfull takeoff
Footing countAdvisory

Whether the design calls for an unusually high number of footings for its size.

Does not cover: A cost and labour signal. Fewer footings is not automatically better, and reducing them changes beam spans that must then be re-checked.

CitesNo code section — this is advice, not a verdict
BasisCalculated from the design
Needs from youdeck size · post count · beam count
Distinct cut lengthsAdvisory

Whether the cut list has proliferated into many one-off lengths.

Does not cover: Crew-time signal only, with no compliance meaning.

CitesNo code section — this is advice, not a verdict
BasisCalculated from the design
Needs from youfull takeoff

Lighting & skirting

2 checks
Lighting circuit sizingAdvisory

Whether the low-voltage transformer covers the fixture load with 25% headroom and the wire gauge holds the voltage drop to the furthest fixture within a volt.

Does not cover: Fixture wattages are typical LED figures, not the product's; the run length is the one you typed. Line-voltage work, GFCI protection, burial depth and the electrical permit are an electrician's and are not evaluated.

CitesNo code section — this is advice, not a verdict
BasisCalculated from the design
Needs from youlighting fixtures · wire run length
Skirting ventilation and accessAdvisory

Whether solid skirting leaves the space under the deck able to breathe, and whether there is a way in for maintenance.

Does not cover: Applies the under-floor ventilation rule of thumb to a deck, which no code requires; lattice and spaced boards are taken to breathe without checking their open area. Drainage and grading under the deck are not evaluated.

CitesNo code section — this is advice, not a verdict
BasisMeasured from the drawing
Needs from youskirting style · ventilated flag

Local amendments

1 check
Local amendmentsAdvisory

Surfaces the amendments recorded for this jurisdiction so they are read before submission.

Does not cover: It repeats what is in our jurisdiction data; it does not enforce it. Most places resolve to a state baseline with no municipal amendments recorded, and an amendment we do not hold is one you will not see here.

CitesVaries by jurisdiction
BasisLocal jurisdiction data
Needs from youlocation

Not modelled at all

9 areas

These are genuine absences rather than partial implementations. Where a design strays into one, DeckForge is built to say so instead of returning a verdict.

Snow, wind, seismic, flood and wildfire loadsSpans are tabulated at 40 psf live. A ground snow load above that escalates the project to professional review rather than resizing anything; wind, seismic, flood and wildfire are not modelled at all.
Anything heavy on the deckA hot tub, outdoor kitchen, roof or pergola can be declared, and each one takes the project out of prescriptive scope. DeckForge does not size the framing they need — it declines to answer.
Multi-level and rooftop decksOne level is modelled. Rooftop decks, decks over living space, and commercial occupancy are out of scope entirely.
Curved and angled outer edgesDetected and refused. No framing is generated for them and no check should be read as covering them.
Soil beyond a presumptive valueOne bearing value per jurisdiction. No site investigation, expansive soils, fill, slopes, retaining walls or high water table.
Property boundariesSetbacks, easements, utilities and lot lines are not modelled. Nothing here checks a deck against a property line.
Connection and guard-post capacityHardware appears in the takeoff and guard height is checked, but the capacity of the post-to-frame connection that resists guard load is not evaluated.
Stair headroomIRC R311.7.2 is not checked — there is no overhead geometry to measure against.
EngineeringDeckForge applies prescriptive tables. It does not perform engineering analysis and is not a substitute for a licensed design professional where one is required.

How local is “local”

83 metro areas have their own recorded code edition, frost depth, soil bearing and amendments. Every other place resolves to its state baseline, which means local amendments for it are unknown to us. Every report says which of the two it used — a state baseline is never presented as local verification.

Local dataA row exists for this city, with its adopted edition and any amendments we hold. Amendments change; confirm with the building department before submitting.
State baselineNo municipal row for this place. Frost depth, permit rules and local amendments may all differ from the state-wide figures used.
No location setGeneric IRC 2021 placeholders, including a 12″ frost depth that is wrong for most of the country. Results are labelled as such and should not be relied on.

What we will not tell you

That your permit is approvedDeckForge produces a set built for permit submission. Approval is the authority having jurisdiction’s decision, and nothing here binds it.
That your deck is safeChecks are run against prescriptive tables for what you entered. What gets built, and what the ground and the house are actually like, are field conditions no drawing settles.
What it will costMaterial figures come from one national rule-of-thumb set, shown as a range and labelled an estimate. Labour is not modelled.
Anything a language model made upNo structural result, span, capacity, quantity, citation or compliance verdict in DeckForge is produced by AI. They come from published tables and arithmetic over what you entered, and the same inputs always give the same answer.